Model
KV-E4XR
Number of inputs
4
Minimum ON voltage
19V
Maximum OFF current
2mA
Input time constant (switchable between 2 levels by using special auxiliary relays 2609 to 2612)
10 ms ± 20%, 10 µs ± 20% for both rising (OFF to ON) and falling (ON to OFF) edges
Number of outputs
4
Output
Relay
Rated load voltage
250 VAC/30 VDC, 2 A (Inductive load), 4 A (Resistive load)
Rated output current
2 A/output (inductive load), 4 A/output (resistive load), 4 A/common
Leakage current (at OFF)
―
Residual voltage (at ON)
Startup operation time (OFF → ON)
10ms or less
Startup operation time (ON → OFF)
ON resistance
50 mΩ or less
Relay life span
Electrical: 100,000 times or more (20 times/minute), mechanical: 20,000,000 times or more
Relay replacement
Not possible
General specifications
Weight
Approx 120g
Input specifications
24 V mode
Input maximum rating
26.4 VDC
Input voltage
24 VDC, 5.3 mA
Input impedance
4.3 kΩ
Common input
4/common
Output specifications
Common output
External connection method
Terminal block