Model
KV-NC32EXT
Expansion input unit
External connection method
Connector
Input Points
32
Input terminals
24 VDC mode
Maximum input voltage
26.4 VDC
Input rated voltage
24 VDC mode
3.6 mA
5 VDC mode
―
Minimum ON voltage
24 VDC mode
19 V
5 VDC mode
―
Maximum OFF current
24 VDC mode
1.5 mA
Maximum OFF voltage
―
Common method
32 points/1 common (2 terminals)*1
Input time constant (four-level switching)
Input time constant setting
OFF to ON: Typ.
25 μs : 10 μs
300 μs : 240 μs
1 ms : 1 ms
10ms : 10 ms
OFF to ON: Max.
25 μs : 50 μs
300 μs : 290 μs
1 ms : 1.2 ms
10ms : 11 ms
ON to OFF: Typ.
25 μs : 50 μs
300 μs : 280 μs
1 ms : 1 ms
10ms : 10 ms
ON to OFF: Max.
25 μs : 150 μs
300 μs : 390 μs
1 ms : 1.2 ms
10 ms : 11 ms
Input impedance
6.3 kΩ
Expansion output unit
Output Points
32
External connectionmethod
MOSFET (N-ch)
(with overcurrent protection function) *2
External connection method
Connector
Rated load
30 VDC 0.2 A *3
Leakage current (when output is OFF)
100 μA or less
Residual voltage (at ON)
0.6 VDC or less
Common method
32 points/1 common (2 terminals) *1
Response time
OFF to ON
100 μs or less (with a load of 1 mA or more)
ON to OFF
200 μs or less (with a load of 1 mA or more)
Internal current consumption
60 mA or less
Weight
Approx. 150 g
*1 The input COM and output COM terminals are independent.
*2 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common, until the cause of the problem is removed.
*3 Rated load of each common is 1.6 A.