Model
KV-N16ET
Expansion output unit
Output Points
16 points
External connectionmethod
MOSFET
With overcurrent protection function *1 *2
External connection method
Terminal block
Rated load
30 VDC, 0.5 A
Leakage current (when output is OFF)
100 μA or less
Residual voltage (at ON)
0.8 VDC or less (with 0.5 A output)
0.6 VDC or less (with 0.3 A output)
ON resistance
−
Common method
16 points/1 common
(8 terminals) *3 *4
Response time
OFF to ON
100 μs or less (with a load of 1 mA or more)
ON to OFF
200 μs or less (with a load of 1 mA or more)
Relay life
−
Relay replacement
Internal current consumption
40 mA or less
Weight
Approx. 210 g
*1 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common (The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015 for the case of the KV-N16ET(P).) , until the cause of the problem is removed.
*2 MOSFET (N-ch) output for the sink output type; and MOSFET (P-ch) output for the source output type.
*3 The KV-N8ET(P) and KV-N16ET(P) COM terminals are shorted internally.
*4 The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015 for the case of the KV-N16ET(P).