Technical data
KM2604
Load type
ohmic, inductive, lamp load
Max. output current
16 A
Number of outputs
4 x change-over
Operation
–
Nominal switching voltage
250 V AC, 30 V DC
Nominal switching current
16 A
Electrical isolation
1.5 kV (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III
Current consumption power contacts
–
Current consumption K-bus
typ. 15 mA
Current consumption 24 V DC
50 mA for each active relay
Bit width in the process image
4 outputs
Switching current
16 A AC/12 A DC at 30 V DC
Operating cycles mech. (min.)
5 x 106
Operating cycles electr. (min.)
1 x 106 (1 A/250 V AC)
Lamp test, electronic ballast
max. 25 A starting current
Minimum permitted load
5 mA at 10 V
Dimensions (W x H x D)
99 mm x 100 mm x 62 mm
Configuration
no address or configuration setting
Weight
approx. 250 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE