Technical data
KM2652
Number of outputs
2 x change-over
Nominal voltage
230 V AC (max. switching voltage 250 V AC)
Switching capacity max.
1.5 kVA
Switching voltage max.
250 V AC
Load type
ohmic, inductive, lamp load
Max. output current
6 A per channel
Minimum permitted load
100 mA at 12 V
Lamp test, electronic ballast
max. 10 A starting current
Current consumption power contacts
–
Current consumption K-bus
typ. 130 mA
Contact material
AgSnO2
Bit width in the process image
4 inputs (status hand, auto, relay ON/OFF), 2 outputs
Operating cycles
106
Operating cycles mech. (min.)
1 x 106
Operating cycles electr. (min.)
1 x 105 (3 A/250 V AC)
Configuration
no address or configuration setting
Special features
manual/automatic operation, switch setting readable
Weight
approx. 110 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE