Technical data
IE1001
Number of inputs
8
Input connections
M8, screw type
Nominal input voltage
24 V DC (-15 %/+20 %)
Input filter
3.0 ms
“0” signal voltage
-3…+5 V (EN 61131-2, type 2)
“1” signal voltage
11…30 V (EN 61131-2, type 2)
Input current
typ. 6 mA (EN 61131-2, type 2)
Sensor supply
from control voltage, max. 0.5 A, short-circuit proof in total
Power supply connection
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image
8 inputs
Current consumption from US (without sensor current)
25 mA
Electrical isolation
channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature
0…+55 °C/-25…+85 °C
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 65/66/67 (conforms to EN 60529)/variable
Approvals/markings
CE, UL