Electrical data
Operating voltage [V] 18…31.6 DC
Max. current consumption from AS-i [mA] 30
Additional voltage supply [V] 20…30 DC; (AUX)
Max. current consumption from additional supply [mA] 4000; (AUX)
Integrated watchdog
yes
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 4
Outputs
Number of digital outputs
4
Circuit
PNP
Voltage range DC [V] 20…30; (AUX)
Max. current load per output [mA] 1000; (utilisation category DC-12: 700 mA; utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Max. current load outputs total [mA] 4000; (> 50 °C: 2000 mA)
Short-circuit proof
yes
Electrically separated
yes
Actuator supply switching outputs
via E+/E- / separate to SELV / AUX
Operating conditions
Ambient temperature [°C] -25…65
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection
IP 20
Protection rating terminals
IP 20
Degree of soiling
2
AS-i classification
AS-i version
2.11; 3.0
AS-i addressing
addressing socket
Extended addressing mode possible
no
AS-i profile
S-8.0.E
AS-i I/O configuration [hex] 8
AS-i ID code [hex] 0.E
AS-i certificate
124403
Assignment of the data bits
data bit
D0
D1
D2
D3
Output
O-1
O-2
O-3
O-4
Mechanical data
Weight [g] 135
Type of mounting
mounting on DIN rail
Materials
plastics; PC-GF20
Displays / operating elements
Display
switching status
LED, yellow O1…O4
operation
LED, green AS-i, AUX
errors
LED, red
Accessories
Accessories (supplied)
cage clamps
Remarks
Pack quantity
1 pcs.
Electrical connection
Connection
pin headers: 4 x ; Spacing: 5.0 mm