Electrical data
Operating voltage [V] 26.5…31.6 DC
Max. current consumption from AS-i [mA] 240
Inputs / outputs
Number of inputs and outputs
Number of digital inputs: 4
Inputs
Number of digital inputs
4
Input circuit of digital inputs
PNP
Sensor supply of the inputs
AS-i
Voltage supply [V] 18…30; (via flat cable)
Max. total current rating of inputs [mA] 200
Input current High [mA] 6…10
Input current Low [mA] 0…2
Min. switching level high signal [V] 11
Digital inputs protected against short circuits
yes
Operating conditions
Ambient temperature [°C] -25…70
Protection
IP 67
AS-i classification
AS-i version
2.1
AS-i addressing
IR addressing possible
Extended addressing mode possible
no
AS-i profile
S-0.0.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] 0.E
AS-i certificate
39101
Assignment of the data bits
data bit
D0
D1
D2
D3
input
1
2
3
4
socket
I-1
I-2
I-3
I-4
pin
2+4
2+4
2+4
2+4
Mechanical data
Weight [g] 114
Type of mounting
AS-i interface to FC lower parts
Materials
PBT; Sealing: FKM; screws: stainless steel
Displays / operating elements
Display
operation
LED, green
errors
LED, red
function
LED, yellow
Accessories
Accessories (optional)
Module lower part
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Pack quantity
1 pcs.
Electrical connection
contact pins to module lower part, FK / PG:
Connector: M12