Electrical data
Operating voltage [V] 26.5…31.6 DC
Max. current consumption from AS-i [mA] 50
Max. current load total [A] 3; (> 50 °C: 2000 mA)
Integrated watchdog
yes
Inputs / outputs
Number of inputs and outputs
Number of digital inputs: 4; Number of digital outputs: 3
Inputs
Number of digital inputs
4
Input circuit of digital inputs
PNP
Sensor supply of the inputs
AUX
Voltage supply [V] 18…30
Max. total current rating of inputs [mA] 200
Input current High [mA] 6…10
Input current Low [mA] 0…2
Min. switching level high signal [V] 11
Digital inputs protected against short circuits
yes
Outputs
Number of digital outputs
3
Circuit
PNP
Voltage range DC [V] 20…30; (external (E+/E-), to PELV)
Max. current load per output [mA] 1000; (utilisation category DC-12: 700 mA; utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof
yes
Electrically separated
yes
Operating conditions
Ambient temperature [°C] -20…70
Note on ambient temperature
cRUus: -25…60 °C
Protection
IP 20
AS-i classification
AS-i version
3.0
AS-i addressing
addressing socket
Extended addressing mode possible
yes
AS-i profile
S-7.A.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.E
AS-i certificate pending
yes
Assignment of the data bits
data bit
D0
D1
D2
D3
input
I-1
I-2
I-3
I-4
Output
O-1
O-2
O-3
–
Mechanical data
Weight [g] 139
Type of mounting
mounting on DIN rail; string mounting possible
Materials
PA
Displays / operating elements
Display
switching status
LED, yellow
operation
LED, green
errors
LED, red
Accessories
Accessories (optional)
COMBICON connectors
Remarks
Pack quantity
1 pcs.
Electrical connection
Connection
COMBICON: