Electrical data
Operating voltage [V] 26.5…31.6 DC
Max. current consumption from AS-i [mA] 250
Max. current load total [A] 3; (> 50 °C: 2000 mA)
Integrated watchdog
yes
Inputs / outputs
Number of inputs and outputs
Number of digital inputs: 4; Number of digital outputs: 3
Inputs
Number of digital inputs
4
Input circuit of digital inputs
PNP
Sensor supply of the inputs
AS-i
Voltage supply [V] 18…30
Max. total current rating of inputs [mA] 200
Input current High [mA] 6…10
Input current Low [mA] 0…2
Min. switching level high signal [V] 11
Digital inputs protected against short circuits
yes
Outputs
Number of digital outputs
3
Circuit
PNP
Voltage range DC [V] 20…30; (external (E+/E-), to PELV)
Max. current load per output [mA] 1000; (utilisation category DC-12: 700 mA; utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof
yes
Electrically separated
yes
Operating conditions
Ambient temperature [°C] -25…70
Note on ambient temperature
cRUus: -25…60 °C
Protection
IP 20
AS-i classification
AS-i version
2.1
AS-i addressing
addressing socket
Extended addressing mode possible
yes
AS-i profile
S-7.A.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.E
AS-i certificate
60701
Assignment of the data bits
data bit
D0
D1
D2
D3
input
I-1
I-2
I-3
I-4
Output
O-1
O-2
O-3
–
Mechanical data
Weight [g] 144
Type of mounting
mounting on DIN rail; string mounting possible
Materials
PA
Displays / operating elements
Display
switching status
LED, yellow
operation
LED, green
errors
LED, red
Accessories
Accessories (optional)
COMBICON connectors
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Pack quantity
1 pcs.
Electrical connection
Connection
COMBICON: