Model
KL-2DA
General specifications
Current consumption
190mA or less
Vibration resistance
10 to 55 Hz, 1.5 mm or less double amplitude for 2 hours in each of the X, Y, and Z directions
Power voltage
24 VDC ± 10%
Operating ambient temperature
0 to 60°C
Operating ambient humidity
35 to 85%RH
Operating environment
Minimal amount of dust and corrosive gas present
Withstand voltage
1,500 VAC for 1 minute (between the batch of external input terminals, the case, and the batch of power supply terminals)
Insulation resistance
50 MΩ or more (between the batch of external input terminals, the case, and the batch of power supply terminals)
Weight
approx 180g
Performance specifications
Conversion speed
250 µs/ch
Total accuracy (25°C)
Voltage
0.2% of F.S.
Current
Total accuracy (0 to 60°C)
Voltage
0.4% of F.S.
Current
Isolation mode
Photocoupler isolation (channels are not isolated from each other)
Noise resistance
Normal mode
500 Vp-p, 1 µs, 50 ns (measured with a noise simulator)
Common mode
1,500 Vp-p (measured with a noise simulator)
Number of analog outputs
2
Output range (resolution)
Voltage
0 to +5V (1.25mV 1/4000)+1 to +5V (1mV 1/4000)0 to +10V (2.5mV 1/4000)-10 to +10V (2.5mV 1/8000)
Current
0 to 20 mA (5 µA 1/4000), 4 to 20 mA (4 µA 1/4000)
Minimum load resistance, maximum load resistance
Voltage
1 kΩ
Current
400 Ω