Model
KL-16CT
General specifications
Disconnection error output load
30 VDC, 0.1 A or less, residual voltage: 1 V or less
Vibration resistance
10 to 55 Hz, 1.5 mm or less double amplitude for 2 hours in each of the X, Y, and Z directions; 1 G when attached to a DIN rail
Insulation system
–
Power voltage
10.8 to 26.4 VDC (for the connector type I/O unit, this is supplied by the dedicated cable)
Operating ambient temperature
0 to 60°C
Operating ambient humidity
35 to 85%RH (no condensation)
Operating environment
No corrosive gas present
Noise immunity
Power supply common: 1,500 V, power supply normal: 500 V, pulse width: 1 ms, 50 ns (by way of a noise simulator)
Withstand voltage
500 VAC for 1 minute (between the power supply terminal and the I/O terminals; excluding the ERR output terminal)
Insulation resistance
–
Performance specifications
Input maximum rating
Input voltage
Minimum ON voltage
Maximum OFF current
Maximum OFF voltage
Input impedance
Number of inputs/outputs
16-connector transistor output
Internal current consumption
70mA or less
Weight
approx 70g
Output specifications
Output
NPN open collector
Residual voltage (when output is ON)
0.8V or less
Leakage current (when output is OFF)
100 µA or less
transistor output
Rated load voltage
30 V DC and
5 to 26.4 V DC (power source supplied across VC and C)
Rated output current
0.5 A/output (when 24 V or more is applied across VC and C), 0.15 A/output (when 12 V or more is applied across VC and C), 0.05 A/output (when 5 V or more is applied across VC and C)
Common ground
Written on the terminal wiring diagram of each unit
ON delay time
25 µs or less
OFF delay time
200 µs or less
Insulation resistance
20 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminals; excluding the ERR output terminal)
Insulation system
Photocoupler isolation
relay output
Rated voltage
–
Rated output current
Common ground
ON resistance
ON delay time
OFF delay time
Insulation resistance
Insulation system