Technical data
EP8309-1022
Protocol
EtherCAT
Bus interface
2 x M8 socket, shielded, screw type
Number of channels
8 digital inputs or outputs (6…13)
Input filter
3 ms
Limit frequency
2.5 kHz
Signal connection
M12, screw type
Number of analog inputs
2, single-ended, 12 bit, 0/4…20 mA (0/2)
Number of analog outputs
1, single-ended, 12 bit, 0/4…20 mA (15)
Number of PWMi outputs
1 x 1.2 A, max. 30 kHz (14)
Nominal voltage
24 V DC (-15 %/+20 %)
Measuring error
input: