Technical data
EP2338-0001
Protocol
EtherCAT
Bus interface
2 x M8 socket, shielded, screw type
Specification
EN 61131-2, type 1/3
Number of channels
8 digital inputs or outputs
Input/output connections
M8, screw type
Input filter
10 µs
“0” signal voltage
-3…+5 V
“1” signal voltage
11…30 V, 6 mA input current (EN 61131-2, type 3)
Sensor supply
from load supply voltage, max. 0.5 A, short-circuit proof in total
Load type
ohmic, inductive, lamp load
Rated load voltage
24 V DC (-15 %/+20 %)
Max. output current
0.5 A per channel, individually short-circuit proof
Short-circuit current
typ. 1.5 A
Auxiliary power current
typ. 20 mA + load
Current consumption from US
120 mA
Power supply connection
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Electrical isolation
500 V
Weight
approx. 165 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings
CE, UL, ATEX
Protect. class/installation pos.
IP 65/66/67 (conforms to EN 60529)/variable
Ex marking
II 3 G Ex nA IIC T4 Gc