Technical data
EP2624-0002
Protocol
EtherCAT
Bus interface
2 x M8 socket, shielded, screw type
Number of outputs
4 x make contacts
Ohmic switching current
0.5 A AC/2 A DC per channel
Output connections
M12, screw type
Minimum permitted load
10 µA at 10 mV DC
Load type
ohmic, inductive, lamp load
Nominal output voltage
25 V AC/30 V DC
Distributed clocks
–
Current consumption from US
200 mA
Power supply connection
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Operating cycles mech. (min.)
1 x 108
Operating cycles electr. (min.)
2 x 105 (1 A/30 V DC)
Electrical isolation
500 V
Special features
potential-free switching
Weight
approx. 165 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 65/66/67 (conforms to EN 60529)/variable
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc