Technical data
EP2816-0004
Protocol
EtherCAT
Bus interface
2 x M8 socket, shielded, screw type
Number of outputs
16
Output connections
M16, 19-pin
Load type
ohmic, inductive, lamp load
Nominal output voltage
24 V DC (-15 %/+20 %)
Max. output current
0.5 A per channel, individually short-circuit proof, ? 4 A
Short-circuit current
max. 1.5 A
Distributed clocks
yes
Current consumption from US
120 mA
Auxiliary power current
typ. 20 mA + load
Power supply connection
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Electrical isolation
500 V
Special features
ideal for multi-pin connector valve terminals
Weight
approx. 165 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 65/66/67 (conforms to EN 60529)/variable
Approvals/markings
CE, UL