Technical data
EL5032
Technology
EnDat 2.2 interface (ordering designation Endat22)
Number of channels
2
Encoder connection
D+, D-, C+, C-
Encoder operating voltage
optionally 5 V DC or 9 V DC, 0.5 A total current (generated from the 24 V DC power contacts)
Supply voltage electronics
24 V DC (via power contacts)
Commands
reading position values including additional information available for selection via MRS code (Memory Range Select), reading and writing parameters, reset functions
Resolution
max. 48 bit position
Current consumption power contacts
typ. 150 mA + load
Current consumption E-bus
typ. 120 mA
Distributed clocks
yes
Special features
saving the zero offset shift, electronic type plate, diagnostics, warning, including cable length compensation up to 100 m, reading the encoder temperature values
Electrical isolation
500 V (E-bus/field potential)
Weight
approx. 50 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE, UL