Technical data
EL3751-0004
Number of inputs
1
Power supply
via the E-bus
Technology
Signal type
differential
Oversampling factor
n = 1…64
Distributed clocks
yes
Distributed clock precision
4 M?
Input filter limit frequency
3 kHz
Dielectric strength
max. 36 V
Connection method
2-, 3-, 4-wire
Conversion time
100 µs/10 ksps
Measuring range, nominal
0…5 k?, RTD, Pt100/Pt1000, Ni, KTY
Measuring range, technical
generally 107 % of the nominal measuring range, see documentation
Resolution
24 bit (incl. sign)
Measuring error
typ. ±0.01 % relative to the respective full scale value @ 23 °C in some measuring ranges, see documentation
Temperature coefficient
typ.