EL3632
Number of inputs
2
Technology
Condition Monitoring (IEPE), oversampling recording
Signal type
differential
Signal voltage
IEPE constant current supply and recording of modulated AC voltage
Distributed clocks
yes
Input filter limit frequency
analog parameterisable 5th order low-pass filter up to 25 kHz, typically 0.05 Hz high-pass filter
Conversion time
20 ?s (max. 50 ksamples/s)
Measuring range
default ±5 V up to 25 kHz, ±250 mV up to 10 Hz
Power supply UV
24 V DC via power contacts
Sensor voltage
max. power contact voltage less 1 V
Sensor state monitoring
yes, through monitoring of the bias voltage
Supply current IEXCITE
typ. 2/4/8 mA (separately configurable for both channels)
Input
single-ended
Resolution
16 bit (incl. sign)
Measuring error