Technical data
EL3602, ES3602
Number of inputs
2 (differential)
Power supply
via the E-bus
Technology
differential input
Signal voltage
-10…+10 V, -5…+5 V, -2.5…+2.5 V, -1.25…+1.25 V (parameterisable)
Oversampling factor
–
Distributed clocks
–
Distributed clock precision
–
Internal resistance
> 200 k?
Input filter limit frequency
3 kHz
Common-mode voltage UCM
max. 35 V
Resolution
24 bit (incl. sign)
Conversion time
20 ms default setting, 1…400 ms configurable
Input signal bandwidth
–
Measuring error
60 dB
Special features
various filter times, limit value monitoring, high precision
Weight
approx. 60 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Relative humidity
95 %, no condensation
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all ESxxxx terminals
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc