Technical data
EL3208
Number of inputs
8
Power supply
via the E-bus
Technology
2-wire
Signal type
single-ended
Distributed clocks
–
Input filter limit frequency
typ. 1 kHz
Sensor types
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 ?…1/4 k?), KTY sensors (types see documentation)
Connection method
2-wire
Conversion time
approx. 170 ms default setting, 3…1600 ms configurable
Measuring current