Technical data
EL3202-0030
Number of inputs
2
Power supply
via the E-bus
Technology
Temperature measurement (RTD)
Distributed clocks
–
Input filter limit frequency
typ. 1 kHz
Sensor types
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 ?…1/4 k?), KTY sensors (types see documentation)
Connection method
4-wire
Measuring range
-200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors); -200…+320 °C (high-precision)
Resolution
0.01 °C per digit
Conversion time
approx. 85 ms default setting, 2…800 ms configurable
Temperature range
-200…+320 °C (Pt sensors)
Measuring current