Technical data
EJ3202
Technology
temperature measurement (RTD)
Connection method
2- or 3-wire (default: 2-wire)
Sensor types
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 ?…1/4 k?), KTY sensors (types see documentation)
Number of inputs
2
Measuring range
-200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors)
Resolution
0.1 °C per digit
Measuring error