Technical data
IL2300-B510
Extension modules
max. 120 with max. 128 byte input and 128 byte output data
Digital peripheral signals
max. 960 inputs and 960 outputs
Analog peripheral signals
max. 60 inputs and 60 outputs
Number of PDOs (CANopen)
16 send and 16 receive process data objects
Additional CANopen features
life, node guarding, emergency object, variable mapping, store/restore
Configuration possibility
through KS2000 or the controller (service data objects)
Data transfer rates
automatic detection of 10 kbaud up to 1 Mbaud
Bus interface
1 x M12 plug, 5-pin
Power supply
control voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type
Power supply connection
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Box supply current
45 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current
according to I/O type
Electrical isolation
control voltage/fieldbus: 500 V, control voltage/inputs or outputs: according to I/O type
Operating/storage temperature
0…+55 °C/-25…+85 °C
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 65/66/67 (conforms to EN 60529)/variable
Approvals/markings
CE, UL