Technical data
KL6811, KS6811
Technology
DALI/DSI
Number of channels
1
Slaves/groups
max. 64/max. 16
Data transfer channels
1
Data transfer standard
DALI
Data transfer rates
1200 baud
Current consumption K-bus
typ. 55 mA
Current consumption power contacts
typ. 30 mA + load
Electrical isolation
500 V (K-bus/DALI-bus)
Bit width in the process image
Input/Output: 3 Byte each
Configuration
via the Bus Coupler or the controller
Nominal voltage
24 V DC (-15 %/+20 %)
Input voltage
24 V DC (-15 %/+20 %)
Insulation voltage
DALI-bus/K-bus: 1,500 V DC, DALI-bus/power contacts: 1,500 V DC
DALI/DSI
standards-compliant, open circuit voltage 11.5…15 V DC
DALI power supply
max. 130 mA
Surge voltage resistance
constant load 275 V ACrms
Special features
connection of up to 64 DALI slaves; TwinCAT library: TwinCAT PLC DALI
Weight
approx. 80 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc