Technical data
KL1362, KS1362
Connection technology
2-wire
Specification
break-in alarm
Number of inputs
2
Nominal voltage
24 V (-15 %/+20 %)
“0” signal current
? 1 mA
“1” signal current
? 1 mA
Operating voltage
5.1 V
Line interruption
3 mA
Cable resistance
? 200 ?
Input filter
3.0 ms
Current consumption K-bus
typ. 35 mA
Electrical isolation
500 V (K-bus/field potential)
Bit width in the process image
4 inputs
Configuration
no address or configuration setting
Special features
monitoring of alarm contacts
Weight
approx. 55 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL, ATEX, DNV GL
Ex marking
II 3 G Ex nA IIC T4 Gc