Technical data
KL2124, KS2124
Connection technology
2-/3-wire
Number of outputs
4
Nominal voltage
5 V DC
Load type
ohmic, inductive, lamp load
Max. output current
±20 mA (short-circuit proof) per channel, 8 mA signal current
Short-circuit current
–
Breaking energy
–
Reverse voltage protection
yes
Electrical isolation
500 V (K-bus/field potential)
Current consumption power contacts
typ. 16 mA + load
Current consumption K-bus
typ. 14 mA
Bit width in the process image
4 outputs
Configuration
no address or configuration setting
Weight
approx. 70 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc