Technical data
KL6211, KS6211
Technology
AS-Interface
Number of channels
1
AS-Interface channels
1
Number of slaves
31 for V 2.0, 62 for V 2.1
Specification version
AS-Interface V 2.0, V 2.1
Slave types
digital and analog
Diagnostics
power failure, slave failure, parameterisation fault
AS-Interface address assignment
via configuration or automatic
Cycle time
max. 5 ms (31 devices)
Connection
2 lines via spring force technology
Current consumption K-bus
typ. 55 mA (K-bus), typ. 60 mA (AS-Interface)
Current consumption power contacts
typ. 60 mA + load
Electrical isolation
500 V (AS-Interface/K-bus)
Power contacts
yes
Bit width in the process image
selectable: 12 bytes, 22 bytes or 38 bytes, of which 6 bytes parameter interface
Configuration
via fieldbus parameter interface, DP-V1 or Bus Coupler through KS2000
Weight
approx. 55 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL
AS-Interface certificate
yes, ZU-No. 125801