Technical data
KL2602, KS2602
Number of outputs
2 x make contacts for power contact
Nominal voltage
230 V AC/30 V DC
Load type
ohmic, inductive, lamp load
Max. output current
5 A per channel
Switching current
5 A AC/DC (ohmic)/2 A AC/DC (inductive)
Ohmic switching current
5 A AC/DC
Inductive switching current
2 A AC/DC
Minimum permitted load
10 mA at 5 V DC
Lamp test, electronic ballast
max. 5 A starting current (4 x 58 W)
Electrical isolation
500 V (K-bus/field potential)
Current consumption power contacts
load only
Current consumption K-bus
typ. 80 mA
Bit width in the process image
2 outputs
Operating cycles mech. (min.)
2 x 107
Operating cycles electr. (min.)
1 x 105 (5 A/30 V DC)
Configuration
no address or configuration setting
Special features
power relay
Weight
approx. 85 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL, ATEX, DNV GL
Ex marking
II 3 G Ex nA IIC T4 Gc