Product characteristics
Output function
normally open
Sensing range [mm] 10
Housing
threaded type
Dimensions [mm] M30 x 1.5 / L = 80
Application
Application
simple evaluation of rotating and linear movement with regard to underspeed; blocking
Electrical data
Nominal voltage AC [V] 20…250
Nominal voltage DC [V] 20…250
Nominal frequency AC [Hz] 45…65
Protection class
II
Reverse polarity protection
yes
Outputs
Total number of outputs
1
Output function
normally open
Max. voltage drop switching output DC [V] 7.5
Minimum load current [mA] 6
Max. leakage current [mA] 1.5
Permanent current rating of switching output AC [mA] 350
Permanent current rating of switching output DC [mA] 100
Short-time current rating of switching output [mA] 2200; ((20 ms / 0,5 Hz))
Short-circuit proof
no
Overload protection
no
Detection zone
Sensing range [mm] 10
Sensing range adjustable
no
Real sensing range Sr [mm] 10 ± 10 %
Operating distance [mm] 0…8.1
Measuring/setting range
Setting range [Imp/min] 5…3600
Accuracy / deviations
Correction factor
steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminium: 0.5 / copper: 0.4
Hysteresis [% of Sr] 10
Response times
Start-up delay [s] 12
Max. damping frequency [Imp/min] 4800
Software / programming
Adjustment of the switch point
multiturn potentiometer
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -25…80
Protection
IP 65; IP 67
Mechanical data
Weight [K40] 296.5
Housing
threaded type
Mounting
flush mountable
Dimensions [mm] M30 x 1.5 / L = 80
Thread designation
M30 x 1.5
Materials
brass special coating; PA; TPE-U
Tightening torque [Nm] 50
Displays / operating elements
Display
switching status
2 x LED, yellow
Electrical connection
Required protection
miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting
Accessories
Accessories (supplied)
lock nuts: 2
Remarks
Remarks
Recommendation Check the safe functioning of the unit after a short circuit.
Electrical connection
Connection
Cable: 2 m, PUR; 2 x 0.5 mm²