Product characteristics
Output function
normally open
Sensing range [mm] 4
Housing
threaded type
Dimensions [mm] M12 x 1
Electrical data
Frequency AC [Hz] 47…63
Operating voltage [V] 20…140 AC / 10…140 DC
Protection class
I
Reverse polarity protection
no
Outputs
Output function
normally open
Max. voltage drop switching output DC [V] 5
Max. voltage drop switching output AC [V] 5
Minimum load current [mA] 5
Max. leakage current [mA] 0.8
Permanent current rating of switching output AC [mA] 200
Permanent current rating of switching output DC [mA] 200
Short-time current rating of switching output [mA] 900; (20 ms / 0,5 Hz)
Switching frequency AC [Hz] 25
Switching frequency DC [Hz] 90
Short-circuit proof
no
Overload protection
no
Detection zone
Sensing range [mm] 4
Real sensing range Sr [mm] 4 ± 10 %
Operating distance [mm] 0…3.25
Accuracy / deviations
Correction factor
steel: 1 / stainless steel: 0.7 / brass: 0.45 / aluminium: 0.4 / copper: 0.33
Hysteresis [% of Sr] 3…15
Switch point drift [% of Sr] -10…10
Operating conditions
Ambient temperature [°C] -25…70
Protection
IP 67
Mechanical data
Weight [K40] 28.2
Housing
threaded type
Mounting
non-flush mountable
Dimensions [mm] M12 x 1
Thread designation
M12 x 1
Materials
brass white bronze coated; sensing face: PC
Tightening torque [Nm] A = 4 mm: 3,5 Nm; B: 5 Nm
Displays / operating elements
Display
switching status
1 x LED, red
Electrical connection
Required protection
miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting
Accessories
Accessories (supplied)
lock nuts: 2
Remarks
Remarks
Recommendation: Check the safe functioning of the unit after a short circuit.
Pack quantity
1 pcs.
Electrical connection – plug
Connector: 1 x 1/2″
Diagrams and graphs