Cảm biến lưu lượng IFM SU9001 16 bar

SKU: SU9001
Hãng sản xuất: IFM
Chất lượng: Mới 100%
Bảo hành: Chính hãng
Chứng từ: CO/CQ, hóa đơn VAT

Mã sản phẩm: SU9001 Danh mục: ,
Liên hệ báo giá

Product characteristics

Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1

Measuring range

0…3170 gph
0…52.84 gpm

Process connection
threaded connection G 1 1/4 flat seal

Application

Special feature
Gold-plated contacts

Application
totaliser function; for industrial applications

Installation
connection to pipe by means of an adapter

Media
water; glycol solutions; coolants; oil

Note on media

low-viscosity oils with viscosity: 7…40 mm²/s (40 °C)

high-viscosity oils with viscosity: 30…68 mm²/s (40 °C)

Medium temperature [°F] 14…176

Pressure rating [bar] 16

Pressure rating [psi] 232

Electrical data

Operating voltage [V] 19…30 DC; (according to EN 50178 SELV/PELV)

Current consumption [mA] 100

Min. insulation resistance [MΩ] 100; (500 V DC)

Protection class
III

Reverse polarity protection
yes

Power-on delay time [s] 10

Inputs / outputs

Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1

Inputs

Inputs
counter reset

Outputs

Total number of outputs
2

Output signal
switching signal; analogue signal; pulse signal; (configurable)

Electrical design
PNP/NPN

Number of digital outputs
2

Output function
normally open / normally closed; (parameterisable)

Max. voltage drop switching output DC [V] 2

Permanent current rating of switching output DC [mA] 250; (per output)

Number of analogue outputs
1

Analogue current output [mA] 4…20; (scalable)

Max. load [Ω] 500

Analogue voltage output [V] 0…10; (scalable)

Min. load resistance [Ω] 2000

Pulse output
flow rate meter

Short-circuit protection
yes

Type of short-circuit protection
pulsed

Overload protection
yes

Measuring/setting range

Measuring range

0…3170 gph
0…52.84 gpm

Display range

0…3804 gph
0…63.4 gpm

Resolution

1 gph
0.02 gpm

Set point SP

7…3170 gph
0.12…52.84 gpm

Reset point rP

0…3163 gph
0…52.72 gpm

Analogue start point ASP

0…2547 gph
0…42.46 gpm

Analogue end point AEP

621…3170 gph
10.36…52.84 gpm

Max. flow rate

3804 gph
63.4 gpm

In steps of

1 gph
0.02 gpm

Volumetric flow quantity monitoring

Pulse value
0.02…9000 * 10³ gal

In steps of
0.02 gal

Pulse length [s] 0,095…2

Temperature monitoring

Measuring range [°F] 14…176

Resolution [°F] 0.5

Set point SP [°F] 14.5…176

Reset point rP [°F] 14…175.5

Analogue start point [°F] 14…144

Analogue end point [°F] 46…176

In steps of [°F] 0.5

Accuracy / deviations

Flow monitoring

Accuracy (in the measuring range)
0,26 gpm)

Response times

Flow monitoring

Response time [s] 0.25; (dAP = 0)

Delay time programmable dS, dr [s] 0…50

Damping for the switching output dAP [s] 0…1

Temperature monitoring

Dynamic response T05 / T09 [s] T09 = 30 (Q > 5 gpm); (water)

Software / programming

Parameter setting options
Flow monitoring; quantity meter; Preset counter; Temperature monitoring

Operating conditions

Ambient temperature [°F] 14…140

Storage temperature [°F] -13…176

Protection
IP 67

Mechanical data

Weight [g] 1859

Materials
housing: AlMgSi0,5 anodised; Sealing: FKM; connector housing: brass Optalloy-plated; PA 6.6; cover film: PA

Materials (wetted parts)
stainless steel (1.4404 / 316L); FKM; PPS; Centellen 200

Process connection
threaded connection G 1 1/4 flat seal

Displays / operating elements

Display

Display unit
5 x LED, green (gpm, gph, gal, °F, 10³)

switching status
2 x LED, yellow

measured values
alphanumeric display, 4-digit

programming
alphanumeric display, 4-digit

Accessories

Accessories (supplied)

sealings: 2, Centellen

Accessories (optional)

adapter for pipe: 1 x 1″ NPT, stainless steel, E40206

Remarks

Remarks

sealing: only with supplied Centellen seals

MW = measured value

MEW = Final value of the measuring range

Pack quantity
1 pcs.

Electrical connection

Connection
Connector: 1 x M12; Moulded body: brass, Optalloy-plated; Contacts: gold-plated