Product characteristics
Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Process connection
threaded connection Rp 1 internal thread
Temperature monitoring
Measuring range [°C] -10…100
Application
Special feature
Gold-plated contacts
Application
for industrial applications
Media
water; glycol solutions; coolants; oil
Note on media
oil 1 with viscosity: 10 mm²/s (40 °C)
oil 2 with viscosity: 46 mm²/s (40 °C)
Medium temperature [°C] -10…100
Pressure rating [bar] 25
Pressure rating [Mpa] 2.5
MAWP (for applications according to CRN) [bar] 25
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] 2 l/min; medium and operating temperature: +22 °C ± 4K)
Repeatability
± 1 % MEW
Temperature monitoring
Temperature drift
0,029 °C / K
Accuracy [K] 3 K (25°C; Q > 1 l/min)
Response times
Flow monitoring
Response time [s] 0.01
Damping for the switching output dAP [s] 0…5
Damping for the analogue output dAA [s] 0…5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 120 (Q > 1 l/min)
Software / programming
Parameter setting options
hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9 CDV
Profiles
Smart Sensor: Process Data Variable; Device Identification
SIO mode
yes
Required master port type
A
Process data analogue
2
Process data binary
2
Min. process cycle time [ms] 5
Supported DeviceIDs
Type of operation
DeviceID
Default
563
Operating conditions
Ambient temperature [°C] 0…60
Note on ambient temperature
medium temperature