Product characteristics
Electrical design
PNP/NPN; (automatic load detection PNP/NPN)
Output function
normally open / normally closed; (selectable)
Sensing range [mm] 15
Communication interface
IO-Link
Housing
threaded type
Dimensions [mm] M30 x 1.5 / L = 90
Electrical data
Operating voltage [V] 10…30 DC; (10…36 DC (60 °C))
Current consumption [mA] 18
Protection class
III
Reverse polarity protection
yes
Outputs
Electrical design
PNP/NPN; (automatic load detection PNP/NPN)
Output function
normally open / normally closed; (selectable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 100
Switching frequency DC [Hz] 10
Short-circuit proof
yes
Overload protection
yes
Detection zone
Sensing range [mm] 15
Accuracy / deviations
Hysteresis [% of Sr] 1…15
Switch point drift [% of Sr] -20…20
Interfaces
Communication interface
IO-Link
Transmission type
COM1 (4,8 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9 CDV
Profiles
Smart Sensor
SIO mode
yes
Min. process cycle time [ms] 101
Supported DeviceIDs
Type of operation
DeviceID
Default
388
Operating conditions
Ambient temperature [°C] -25…80
Protection
IP 65; IP 67
Mechanical data
Weight [g] 118.55
Housing
threaded type
Mounting
non-flush mountable
Dimensions [mm] M30 x 1.5 / L = 90
Thread designation
M30 x 1.5
Materials
housing: stainless steel (1.4404 / 316L); pushbuttons: TPE-U; cover: PBT; plug: PEI
Displays / operating elements
Display
switching status
1 x LED, yellow
Teach function
yes
Electronic lock
yes
Accessories
Accessories (supplied)
lock nuts: 2
Remarks
Pack quantity
1 pcs.
Electrical connection – plug
Connector: 1 x M12