Technical data
KL2692, KS2692
Connection technology
2-wire
Number of outputs
2 potential-free relay outputs (normally-open contacts)
Number of inputs
2 digital 24 V inputs
Nominal voltage
30 V DC
Max. output current
3 A per channel
Ohmic switching current
5 A AC/DC per channel
Inductive switching current
2 A AC/DC per channel
Minimum permitted load
10 mA at 5 V DC
Electrical isolation
500 V (K-bus/field potential)
Current consumption power contacts
–
Current consumption K-bus
typ. 165 mA
Bit width in the process image
2 x 8 bit data, 1 x 8 bit control/data
Operating cycles mech. (min.)
2 x 107
Operating cycles electr. (min.)
1 x 105 (5 A/30 V DC)
Configuration
via the Bus Coupler or the controller
Weight
approx. 60 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL