Technical data
KL2612, KS2612
Number of outputs
2 x change-over
Nominal voltage
125 V AC/30 V DC
Load type
ohmic
Max. output current
2 A per channel
Switching current
0.5 A AC/2 A DC (ohmic)
Ohmic switching current
0.5 A AC/2 A DC
Inductive switching current
no data
Minimum permitted load
10 µA at 10 mV
Lamp test, electronic ballast
max. 2 A starting current
Electrical isolation
500 V (K-bus/field potential)
Current consumption power contacts
–
Current consumption K-bus
typ. 60 mA
Bit width in the process image
2 outputs
Operating cycles mech. (min.)
1 x 108
Operating cycles electr. (min.)
2 x 105 (1 A/30 V DC)
Configuration
no address or configuration setting
Special features
signal relay
Weight
approx. 80 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals/markings
CE, UL, ATEX, DNV GL
Ex marking
II 3 G Ex nA IIC T4 Gc