Technical data
BC9191
Number of Bus Terminals
64
Max. number of bytes fieldbus
512 byte input and 512 byte output
Ethernet interface
2 x RJ45 (switched)
Protocol
TwinCAT ADS, Modbus TCP
Digital inputs
3 contacts (e.g. window contact, dew point, occupancy sensor)
Analog inputs
3 x 0…10 V (e.g. CO2 sensor, air quality sensor, brightness sensor) 1 x PT/Ni1000 (-20…+60 °C) for air temperature measurement 1 x resistance measurement for set value specification (0…10 K?)
Digital outputs
1 x 10 mA, LED output (max. 24 V) 1 x 230 V AC, 10 A, relay (e.g. air heater) 3 x 230 V AC, 1 A, relay (3-stage fan) 2 x 230 V AC, 1 A, triac (e.g. valves for heating and cooling)
Analog outputs
2 x 0…10 V (e.g. volumetric air flow controller)
Bus interface
2 x RJ45 (switched)
Sub bus system
Connection to KL6583 (EnOcean)
Supply voltage
230 V AC
Current supply K-bus
200 mA
Dimensions (W x H x D)
118 mm (127 mm with end cover and DIN rail mounting) x 100 mm x 70 mm
Weight
approx. 345 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Protect. class/installation pos.
IP20/vertical
Approvals/markings
CE