Application
Application
Flow monitoring; Temperature monitoring; Wire monitoring
Electrical data
Operating voltage tolerance [%] -15…15
Operating voltage [V] 24 DC
Current consumption [mA] 100
Reverse polarity protection
no
Power-on delay time [s] 10
Number of channels
1
Outputs
Performance in case of a fault
Relay de-energised in case of the following faults: wire break, reverse polarity or short circuit of the sensor cable, undervoltage, internal fault
Electrical design
relay
Contact rating
4 A (250 V AC cos phi > 0,7) ; 0,2 A (250 V DC); 4 A (24 V DC)
Switching function flow monitoring
relay energised when flow is present
Switching function temperature monitoring
relay de-energised when temperature is exceeded
Short-circuit proof
no
Overload protection
no
Software / programming
Adjustment of the switch point
programming buttons
Operating conditions
Ambient temperature [°C] -20…60
Storage temperature [°C] -25…80
Protection
IP 20
Protection rating terminals
IP 20
Mechanical data
Weight [g] 369
Housing
housing for DIN rail mounting
Dimensions [mm] 104.5 x 32.5 x 113.6
Materials
PA
Displays / operating elements
Display
fault
LED, red
function
LED, bar graph
switching status
LED, yellow
Electrical connection
Required protection
miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting; Place the fuse outside the hazardous area.
Remarks
Remarks
Caution The control monitor must be mounted outside the hazardous area.
Recommendation Check the safe functioning of the unit after a short circuit.
Pack quantity
1 pcs.
Electrical connection
Connection
terminals: 15 x …2.5 mm²