Application
Application
Flow monitoring; Wire monitoring
Electrical data
Operating voltage tolerance [%] -10…10
Operating voltage [V] 24 DC
Current consumption [mA] 125
Reverse polarity protection
no
Power-on delay time [s] 30
Number of channels
1
Outputs
Electrical design
relay
Contact rating
4 A (250 V AC cos phi > 0,7) ; 0,2 A (250 V DC); 4 A (24 V DC)
Switching function flow monitoring
relay energised when flow is present
Switching function wire break monitoring
relay de-energised in case of wire break
Short-circuit proof
no
Overload protection
no
Software / programming
Adjustment of the switch point
potentiometer
Selection liquids / gases
slide switch
Operating conditions
Ambient temperature [°C] -20…60
Protection
IP 40
Protection rating terminals
IP 20
Mechanical data
Weight [g] 412.5
Housing
housing for DIN rail mounting
Dimensions [mm] 78 x 45 x 120
Materials
plastics
Displays / operating elements
Display
function
11 x LED
switching status
LED, red
Electrical connection
Required protection
miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting; Place the fuse outside the hazardous area.
Remarks
Remarks
Caution The control monitor must be mounted outside the hazardous area.
Recommendation Check the safe functioning of the unit after a short circuit.
Pack quantity
1 pcs.
Electrical connection
Connection
terminals: 15 x …2.5 mm²