Model
FD-G80
Pipe size
DN (Diameter Nominal)
65 A, 80 A
NPS (Nominal Pipe Size)
2 1/2″, 3″
Outer diameter of pipe
ø72 to 78 mm 2.83″ to 3.07″, ø86 to 92 mm 3.39″ to 3.62″
Pipe thickness
2.9 to 6.3 mm 0.114″ to 0.25″
Supported pipe materials
Iron, steel, stainless steel
Supported fluids
Air, Nitrogen, other gases*1
Fluid temperature
0 to 60ºC 32 to 140 °F
Recommended pressure
0.4 MPa or greater (58 PSI or greater)
Rated velocity of flow range
Up to 15 m/s
Actual flow rate range (typical)
m3/h
Pipe size 65 A: 200.0
Pipe size 80 A: 280.0
L/min
Pipe size 65 A: 3300
Pipe size 80 A: 4600
CFM
Pipe size 65 A: 120.00
Pipe size 80 A: 160.00
Standard flow rate range (typical) [CFM]
20°C 68°F 60 psi 0.41 MPa
Pipe size 65 A: 568.43
Pipe size 80 A: 757.91
20°C 68°F 80 psi 0.55 MPa
Pipe size 65 A: 720.64
Pipe size 80 A: 960.85
20°C 68°F 100 psi 0.69 MPa
Pipe size 65 A: 872.84
Pipe size 80 A: 1163.79
20°C 68°F 120 psi 0.83 MPa
Pipe size 65 A: 1025.05
Pipe size 80 A: 1366.73
Display
QVGA 2.2″ LCD color monitor
Display update cycle
Approx. 3 Hz
Display resolution
Instantaneous flow rate
0.1 m3/h, 1 L/min, 0.01 CFM
Consumption/leakage amount
0.01 m3, 1 L, 1 CF
Response time
1.0 s/2.5 s/5.0 s/10.0 s/30.0 s/60.0 s/120.0 s/200.0 s (variable)
Measurement accuracy
Between 10 and 100% of F.S.
±2.0% of RD*2*3*4*5
Between 1 and 10% of F.S.
±1.0% of F.S.*2*3*4*5
Zero point error
±0.15% of F.S.*2*6
Static leakage repeatability
±1.0% of RD*4*7
Hysteresis
Variable
Flow units
CFM(S), CFM, m3/h (N), m3/h (S), m3/h, L/min (N), L/min (S), L/min
I/O wiring connection port
M12 4-pin connector (male)
Detection mode (switchable)
ch.1
Instantaneous flow mode/area mode/pulse (+) mode/integrated flow mode/warning mode (consump)*8
ch.2
Instantaneous flow mode/area mode/pulse (−) mode/warning mode (leak)/error output mode/analog output/integrated flow reset/flow rate zero input/origin adjustment input*8
Standard I/O (switchable)
Control output (ch.1/ch.2)
NPN/PNP setting switchable, open collector output 30 VDC or less, max. 100 mA/ch, residual voltage: 2.5 V or less
Analog output (ch.2)
4 to 20 mA/0 to 20 mA, load resistance: 500 Ω or less
External input (ch.2)
Short-circuit current: 1.5 mA or less, input time: 20 ms or more
Protection circuit
Power supply reverse connection protection, power supply surge protection, short-circuit protection for each output, surge protection for each output
Analog input (for volume conversion)
M8 4-pin connector (female), analog current input (4 to 20 mA), input resistance: 100Ω or less
Power supplied to pressure sensor
Supply voltage: Equivalent to voltage applied to the FD-G, Supply current:70 mA or less (analog output of the pressure sensor included)
Communication interface
USB
USB 2.0
Ethernet
Standard
IEEE 802.3u (100BASE-TX)
Transmission rate
100 Mbps
Cable
Category 5 or higher STP (shielded twisted pair) or UTP (unshielded twisted pair) cable
Connector
M12 connector (female, D-code)
Network function
Modbus TCP, EtherNet/IPTM, IO-Link*9
Recording capacity
Consumption amount/ leakage amount
Approx. 5 years
Events
100
Power supply
Power voltage
20 to 30 VDC including 10% ripple (P-P), Class 2
Power consumption
350 mA or less at 20 V, 290 mA or less at 24 V, 230 mA or less at 30 V (load current excluded) (analog output of the pressure sensor excluded),
550 mA or less at 20 V, 490 mA or less at 24 V, 430 mA or less at 30 V (Maximum load current excluded) (analog output of the pressure sensor excluded)
Environmental resistance
Enclosure rating
IP65/67 (IEC 60529)*10
Ambient temperature
Detection head: −10 to +60°C 14 to 140°F (no freezing), display unit: −10 to +55°C 14 to 131°F (no freezing)
Relative humidity
5 to 85%RH (no condensation)
Vibration resistance
10 to 500 Hz, power spectral density: 0.816 G2/Hz, XYZ axes
Shock resistance
100 m/s2, 16 ms pulse, XYZ axes, 1000 times for each axis
Material
Display unit
Body: PBT + coating, display: PMMA, Power supply port: SUS304-equivalent, Ethernet port: zinc nickel plating
Detection head
Body: PPS/SUS304, rear surface: rubber
Mounting/damping bracket
SUS304
Weight
Approx. 3.6 kg
*1 The gas must be uniform and capable of transmitting ultrasonic waves. Measurement may be unstable due to the pressure inside of the pipe and the type of gas.
*2 This value is guaranteed by KEYENCE inspection facilities. Errors will be introduced by factors such as the type and status of the pipe and the type and temperature of the gas.
*3 This is the value when considering linearity + span error in a stable environment with a temperature of 25°C 77°F.
*4 Defined with stable velocity of flow distribution. Does not include pulsations and fluctuations in the velocity of flow distribution primarily attributable to the equipment.
*5 The linearity error characteristic due to the pipe is not included in this value.
*6 It is possible to reduce zero point errors by performing an origin adjustment.
*7 This is the value within the range where measurement accuracy is guaranteed.
*8 When Bi-directional is specified, the following functions cannot be used. The selection of the comparison view/leak ratio view/static leakage, the measurement/display of the leakage amount/integrated flow, the setting of the target value/warning set value, and money conversions. Also, the I/O settings are limited as shown below.
• ch.1: Pulse(+) mode
• ch.2: Pulse(-) mode, Error output mode, Integrated flow reset, Flow zero input, Origin adjustment input
*9 IO-Link: Compatible with specification v1.1/COM1 (4.8 kbps). IO-Link is a trademark or registered trademark of PROFIBUS Nutzerorganisation e.V. (PNO).
*10 The IP65/67 enclosure rating is lost when a USB connection is established.