Product characteristics
Output function
normally open
Sensing range [mm] 4
Housing
rectangular
Dimensions [mm] 40 x 12 x 26
Electrical data
Operating voltage [V] 20…250 AC/DC
Protection class
II
Reverse polarity protection
yes
Outputs
Output function
normally open
Max. voltage drop switching output DC [V] 6
Max. voltage drop switching output AC [V] 6.7
Minimum load current [mA] 5
Max. leakage current [mA] 2.0 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC)
Permanent current rating of switching output AC [mA] 250; (350 (…50 °C))
Permanent current rating of switching output DC [mA] 100
Short-time current rating of switching output [mA] 2200; (50 ms / 1 Hz)
Switching frequency AC [Hz] 25
Switching frequency DC [Hz] 50
Short-circuit proof
no
Overload protection
no
Detection zone
Sensing range [mm] 4
Real sensing range Sr [mm] 4 ± 10 %
Operating distance [mm] 0…3.25
Accuracy / deviations
Correction factor
steel: 1 / stainless steel: 0.9 / brass: 0.6 / aluminium: 0.5 / copper: 0.4
Hysteresis [% of Sr] 1…20
Switch point drift [% of Sr] -10…10
Operating conditions
Ambient temperature [°C] -25…80
Protection
IP 67
Mechanical data
Weight [g] 103.9
Housing
rectangular
Mounting
non-flush mountable
Dimensions [mm] 40 x 12 x 26
Materials
PBT
Displays / operating elements
Display
switching status
1 x LED, yellow
Electrical connection
Required protection
miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting
Remarks
Remarks
Recommendation: Check the safe functioning of the unit after a short circuit.
Pack quantity
1 pcs.
Electrical connection
Connection
Cable: 2 m, PVC; 2 x 0.5 mm²