Product characteristics
Number of inputs and outputs
Number of digital outputs: 1; Number of analogue outputs: 1
Probe length L [mm] 150…2000
Process connection
G 1 Aseptoflex Vario
Application
Special feature
Gold-plated contacts
Media
Liquids
Dielectric constant of the medium
> 5
Recommended media
water; hydrous media
Medium temperature [°C] -40…150; (For 3-A applications, the medium temperature is limited to 121 °C and COP cleaning is required.)
Tank pressure [bar] -1…40
MAWP (for applications according to CRN) [bar] 25
Electrical data
Operating voltage [V] 18…30 DC
Current consumption [mA] 5
Accuracy / deviations
Measuring error [mm] ± 7
Offset error [mm] 5
Resolution [mm] 1
Zero signal (current) [mA] 4.0
Full signal (current) [mA] 20
Temperature drift per 10 K
± 0.2 %
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode
yes
Required master port type
A
Process data analogue
1
Process data binary
2
Min. process cycle time [ms] 2.3
Supported DeviceIDs
Type of operation
DeviceID
Default
478
Operating conditions
Ambient temperature [°C] -40…80
Storage temperature [°C] -40…100
Protection
IP 68; IP 69K
Mechanical data
Weight [g] 401.5
Materials
stainless steel (1.4404 / 316L); PEI; PFA; PBT; FKM
Materials (wetted parts)
stainless steel (1.4404 / 316L); PEEK; EPDM
Process connection
G 1 Aseptoflex Vario
Surface characteristics Ra/Rz of the wetted parts