Product characteristics
Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
80…4800 gph
1.3…80 gpm
Process connection
threaded connection 1 1/2″ NPT DN40
Application
Special feature
Gold-plated contacts
Application
totaliser function; empty pipe detection; for industrial applications
Media
conductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: 4 gpm)
Response times
Flow monitoring
Response time [s] 0.35; (dAP = 0)
Delay time programmable dS, dr [s] 0…50
Damping for the switching output dAP [s] 0…5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 3 (Q > 4 gpm)
Software / programming
Parameter setting options
Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9 CDV
Profiles
Smart Sensor: Process Data Variable; Device Identification
SIO mode
yes
Required master port type
A
Process data analogue
3
Process data binary
2
Min. process cycle time [ms] 5
Supported DeviceIDs
Type of operation
DeviceID
Default
392
Operating conditions
Ambient temperature [°F] 14…140
Storage temperature [°F] -13…176
Protection
IP 65; IP 67
Mechanical data
Weight [g] 2755.95
Materials
stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U
Materials (wetted parts)
stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; FKM
Process connection
threaded connection 1 1/2″ NPT DN40
Displays / operating elements
Display
Display unit
6 x LED, green (gpm, gph, gal, °F, 10³, 1000 x 10³)
switching status
2 x LED, yellow
measured values
alphanumeric display, 4-digit
programming
alphanumeric display, 4-digit
Accessories
Accessories (supplied)
Label
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Pack quantity
1 pcs.
Electrical connection
Connection
Connector: 1 x M12; Contacts: gold-plated