Product characteristics
Number of inputs and outputs
Number of digital outputs: 1; Number of analogue outputs: 1
Measuring range
-25…160 °C
-13…320 °F
Process connection
diameter Ø 6 mm
Installation length EL [mm] 100
Application
Special feature
Gold-plated contacts
Measuring element
1 x Pt 1000
Reference element
1 x NTC
Media
liquids and gases
Pressure rating [bar] 160
Electrical data
Operating voltage [V] 18…32 DC; (“supply class 2” to cULus)
Current consumption [mA] 10; (24 V)
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s] 6
Integrated watchdog
yes
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
analogue signal; IO-Link; calibration check status
Electrical design
PNP/NPN
Number of digital outputs
1
Output function
normally open; (diagnostic signal)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 100
Diagnostic output
calibration check status and error diagnostics
Number of analogue outputs
1
Analogue current output [mA] 4…20
Max. load [Ω] (Ub – 15 V) x 50
Short-circuit protection
yes
Type of short-circuit protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range
-25…160 °C
-13…320 °F
Note on measuring range
scalable
Factory setting
-10…150 °C / 14…302 °F
Calibration check limit [K] 0.5…3
In steps of [K] 0.05
Resolution
Resolution of analogue output [K] 0.05
Accuracy / deviations
Precision analogue output [K] ± 0,2
Precision IO-Link [K] ± 0,2
Temperature coefficient analogue output [% of the span / 10 K]