Technical data
KL9020
Number of coupler terminals
up to 31 KL9050
Current load
–
Power LED
–
Defect LED
–
Type/number of peripheral signals
Bus Coupler dependency
Max. number of bytes fieldbus
Bus Coupler dependency
Distance between stations
max. 5 m between KL9020 and KL9050
Bus interface
1 x RJ45 socket
Starting current
–
Current consumption K-bus
typ. 70 mA
Current supply K-bus
–
Power contacts
max. 24 V DC/max. 10 A
Nominal voltage
–
Electrical isolation
500 V (power contact/supply voltage/K-bus)
Configuration possibility
none, automatic
PE contact
–
Shield connection
–
Electrical connection to DIN rail
–
Special features
end terminal for K-bus extension
Weight
approx. 45 g
Operating/storage temperature
0…+55 °C/-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE, UL, ATEX, DNV GL
Ex marking
II 3 G Ex nA IIC T4 Gc