Technical data
BX5100
Number of Bus Terminals
64 (255 with K-bus extension)
Max. number of bytes fieldbus
32 Tx/Rx PDOs
Max. number of bytes process image
2048 byte input and 2048 byte output
Digital peripheral signals
2,040 inputs/outputs
Analog peripheral signals
512 inputs/outputs
Data transfer rates
automatic detection up to 1 Mbaud
Bus interface
open style connector, 5-pin
Serial interface
COM1: 1 x RS232, COM2: 1 x RS232 or RS485
SSB
CANopen-based subsidiary bus system for the connection of further peripheral devices
Diagnostics LED
2 x power supply, 2 x K-bus
Display
FSTN display with 2 x 16 characters for diagnosis or own texts, illuminated
Switch
joystick switch for parameterisation and diagnosis
Clock
battery-powered real-time clock for time and date
Power supply
24 V DC (-15 %/+20 %)
Input current
140 mA + (total K-bus current)/4, 500 mA max.
Starting current
2.5 x continuous current
Current supply K-bus
1450 mA
Power contacts
max. 24 V DC/max. 10 A
Electrical isolation
500 V (power contact/supply voltage)
Weight
approx. 250 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE, UL