Technical data
EL6224
Technology
IO-Link input/output
Specification version
IO-Link V1.1
IO-Link interfaces
4
Field voltage
24 V DC via power contacts
Connection
3-wire
Data transfer rates
4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Cable length
max. 20 m
Power supply
via E-bus and power contacts
Electrical isolation
500 V (E-bus/signal voltage)
Power contacts
yes
Supply current for devices
500 mA per device
Current consumption E-bus
typ. 120 mA
Special features
each channel parameterisable in TwinCAT
Weight
approx. 60 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc