Technical data
EL6731-0010
Technology
PROFIBUS slave terminal
Cycle time
differing DP cycle times per slave are possible using the CDL concept
Fieldbus
PROFIBUS DP (standard), PROFIBUS DP-V1 (Cl. 1+2: acyclic services, alarms), DP-V2, PROFIBUS MC (equidistant)
Number of fieldbus channels
1
Data transfer rates
9.6 kbaud…12 Mbaud
Interfaces
1 x D-sub socket, 9-pin, galvanically decoupled
Bus device
max. 125 slaves with up to 244 bytes input, output, parameter, configuration or diagnostic data per slave
Hardware diagnosis
status LEDs
Distributed clocks
–
Bit width in the process image
total max.: 1.4 kbyte input and 1.4 kbyte output data
Current consumption power contacts
–
Current consumption E-bus
typ. 350 mA
Weight
approx. 70 g
Operating/storage temperature
-25…+60 °C/-40…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Approvals/markings
CE, UL, ATEX
Ex marking
II 3 G Ex nA IIC T4 Gc